Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T07FR00137
Case Details
Entered Date:
01/17/2007
Applicant:
DND NEFFSON CO
Description:
Full fire inspection done by Inspector John Bieg 1-17-07.
Outstanding Inspections
Case Number: T07FR00137
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/17/2007 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | TFC 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. 1. Remove storage from blocking sprinkler heads in back stock room. |
01/17/2007 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. 1. Mount extinguisher in back stock room. |
01/17/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1011.2 Illumination. Exit signs shall be internally or externally illuminated. 1. Exit sign shall be illuminated. {main front exit}. 2. Exit sign shall be illuminated. {Rear exit}. |
01/17/2007 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1026.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: Grop M 1. Repair emergency egress lighting. |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00137
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/01/2007 | INSP - FULL | JBURGE | Approved | All Tucson Fire Code violations were corrected on 1-31-07. Inspector John Bieg. |