Description:

Full fire inspection done by Inspector John Bieg 1-17-07.

Outstanding Inspections

Case Number: T07FR00137
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
01/17/2007 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. 1. Remove storage from blocking sprinkler heads in back stock room.
01/17/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. 1. Mount extinguisher in back stock room.
01/17/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1011.2 Illumination. Exit signs shall be internally or externally illuminated. 1. Exit sign shall be illuminated. {main front exit}. 2. Exit sign shall be illuminated. {Rear exit}.
01/17/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1026.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: Grop M 1. Repair emergency egress lighting.

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00137
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
02/01/2007 INSP - FULL JBURGE Approved All Tucson Fire Code violations were corrected on 1-31-07. Inspector John Bieg.