Case: T07FR00137

Parcel: 10511061R


Addresses:

4500 N ORACLE RD


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T07FR00137

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
01/17/2007 VIOL - MEANS OF EGRESS Correction Required TFC 1011.2 Illumination. Exit signs shall be internally or externally illuminated.
1. Exit sign shall be illuminated. {main front exit}.
2. Exit sign shall be illuminated. {Rear exit}.
01/17/2007 VIOL - MEANS OF EGRESS Correction Required TFC 1026.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: Grop M
1. Repair emergency egress lighting.