Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

01/04/2007

Applicant:

DND NEFFSON CO

Description:

Full fire Inspection done by Inspector John Bieg. 1-4-07.

Outstanding Inspections

Case Number: T07FR00038
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 12
End Date Description Inspector Results Comments
01/04/2007 INSP - FULL JBURGE Correction Required Please correct the following Tucson Fire Code violations:
01/04/2007 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required TFC 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. 1. Replace missing ceiling tiles, second floor corridor behind Lane Bryant. 2. Repair hole in ceiling, second floor, sprinkler system riser room at the end of the Lane Bryant exit corridor. 3. Replace missing ceiling tile, on second floor, in the exit corridor behind Fletcher's Music. 4. Replace missing ceiling tile, on second floor, in the corridor behind Radio Shack. 5. Replace missing ceiling tile, on second floor, in the corridor by Payless Shoes. 6. Repair hole in wall, on second floor, in stairwell behind Victoria's Secret. 7. Replace missing ceiling tile, on second floor, in exit corridor behind Eddie Bauer. 8. Replace missing ceiling tile, on second floor, in service 4-A. 9. Repair hole in wall, on second floor, in janitors closet behind mall offices. 10. Replace all missing and broken ceiling tiles, on first floor, in the service corridor behind the food court. 11. Repair holes in walls, on first floor, in the service corridor behind the food court. 12. Repair hole in wall, on first floor, in the corridor by the exit near the main dock. 13. Replace all missing ceiling tiles, on first floor, in the corridor behind Gap. 14. Replace all missing ceiling tiles, on first floor, in the corridor behind Red Robin. 15. Repair hole in wall, on first floor, in the corridor behind Red Robin. 16. Replace all missing ceiling tiles, on the first floor, in the exit corridor behind Ann Taylor's. 17. Replace all missing ceiling tiles, on first floor, in the exit corridor behind Old Navy.
01/05/2007 VIOL - ADMINISTRATION JBURGE Correction Required TFC 107.1 Maintenance of safeguards. Whenever or wherever any device, equipment, system, condition, arrangement, level of protection, or any other feature is required for compliance with the provisions of this code, or otherwise installed, such device, equipment, system, condition, arrangement, level of protection, or other feature shall thereafter be continuously maintained in accordance with this code and applicable referenced standards. 1. Repair or remove non-required Exit sign, on first floor, in storage room/deadend behind Charlotte Russe. 2. Repair exit sign so it reads EXIT on both sides of the sign, first floor, in the corridor behind Old Navy. 3. Repair exit sign, on first floor, in exit corridor between Macy's and Mervyn's. {Missing face plate}. 4. Repair exit sign, on first floor, in exit corridor by Just Sports. Call me if you have any questions at 791-4014.
01/05/2007 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2.2 Means of egress. Combustible materials shall not be stored in exits or exit enclosures. 1. Remove storage from exit corridor, on second floor, corridor to security office. 2. Remove storage from, first floor service 4&5. 3. Remove storage from, first floor Exit corridor behind Ann Taylor's. 4. Remove storage from, first floor Exit stairwell below Payless Shoes. 5. Remove storage from, first floor Exit corridor by Macy's. 6. Remove storage from, first floor Exit corridor between Macy's and Mervyn's.
01/05/2007 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2.3 Equipment rooms. Combustible material shall not be stored in boiler rooms, mechanical rooms or electrical equipment rooms. 1. Remove storage from electrical room, on first floor, in covered parking electrical room.
01/05/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. 1. Place an approved "blank" in the 4-A2 electrical pannel, on second floor, in 4-A electrical room.
01/05/2007 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. 1. Replace electrical box covers on exposed wires, on second floor, in the 3-A riser room. 2. Replace electrical box cover on exposed wires, on first floor, in riser room #4.
01/05/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. 1. Replace missing FDC inlet cover, on first floor, in Disney loading area. 2. Replace missing FDC inlet cover, on first floor, by Chick-fil-A.
01/05/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. 1. Extinguisher in service point 6 {S-6} shall be mounted, on first floor, in Disney corridor.
01/05/2007 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 912.2.2 Existing buildings. On existing buildings, wherever the fire department connection is not visible to approaching fire apparatus, the fire department connection shall be indicated by an approved sign mounted on the street front or on the side of the building. Such sign shall have the letters “FDC” at least 6 inches (152 mm) high and words in letters at least 2 inches (51 mm) high or an arrow to indicate the location. All such signs shall be subject to the approval of the fire code official. 1.The FDC connection shall be visible to approaching fire apparatus. Post a sign on the building indicating the location of the connection. The FDC connection is located by the second floor Lane Bryant exit. 2.The FDC connection shall be visible to approaching fire apparatus. Post a sign in an approved location indicating the direction of the fire department connection. FDC located on the second floor by the 3-A riser room. 3.The FDC connection shall be visible to approaching fire apparatus. Post a sign in an approved location indicating the direction of the fire department connection. FDC located on the second floor by service point seven, {S-7}. 4.The FDC connection shall be visible to approaching fire apparatus. Post a sign in an approved location indicating the direction of the fire department connection. FDC located on the first floor in the Red Robin loading dock. 5.The FDC connection shall be visible to approaching fire apparatus. Post a sign in an approved location indicating the direction of the fire department connection. FDC located on the first floor in the Disney loading area. 6.The FDC connection shall be visible to approaching fire apparatus. Post a sign in an approved location indicating the direction of the fire department connection. FDC located on the first floor by Chick-fil-A.
01/05/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. 1. An exit sign shall be installed for second floor balcony exit, by Red Robin. 2. An exit sign shall be installed for second floor exit behind Payless Shoes. 3. An exit sign shall be installed for second floor exit, in stairwell #2 behind Payless Shoes. 4. An exit sign shall be installed for second floor exit, in stairwell by service 7, {S-7}.
01/05/2007 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1011.2 Illumination. Exit signs shall be internally or externally illuminated. 1. Exit sign shall be illuminated, in second floor exit corridor behind Fletcher's Music. 2. Exit sign shall be illuminated, on second floor balcony exit, by Red Robin. 3. Exit sign shall be illuminated, on second floor, in exit corridor behind Radio Shack. 4. Exit sign shall be illuminated, on second floor, by restrooms next to Victoria's Secret.