Case: T07FR00038

Parcel: 10511061R


Addresses:

4500 N ORACLE RD


Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T07FR00038

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
01/05/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 912.2.2 Existing buildings. On existing buildings, wherever the fire department connection is not visible to approaching fire apparatus, the fire department connection shall be indicated by an approved sign mounted on the street front or on the side of the building. Such sign shall have the letters “FDC” at least 6 inches (152 mm) high and words in letters at least 2 inches (51 mm) high or an arrow to indicate the location. All such signs shall be subject to the approval of the fire code official.
1.The FDC connection shall be visible to approaching fire apparatus. Post a sign on the building indicating the location of the connection. The FDC connection is located by the second floor Lane Bryant exit.
2.The FDC connection shall be visible to approaching fire apparatus.
Post a sign in an approved location indicating the direction of the fire department connection. FDC located on the second floor by the 3-A riser room.
3.The FDC connection shall be visible to approaching fire apparatus. Post a sign in an approved location indicating the direction of the fire department connection. FDC located on the second floor by service point seven, {S-7}.
4.The FDC connection shall be visible to approaching fire apparatus.
Post a sign in an approved location indicating the direction of the fire department connection. FDC located on the first floor in the Red Robin loading dock.
5.The FDC connection shall be visible to approaching fire apparatus.
Post a sign in an approved location indicating the direction of the fire department connection. FDC located on the first floor in the Disney loading area.
6.The FDC connection shall be visible to approaching fire apparatus.
Post a sign in an approved location indicating the direction of the fire department connection. FDC located on the first floor by Chick-fil-A.
01/05/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions.
1. Extinguisher in service point 6 {S-6} shall be mounted, on first floor, in Disney corridor.
01/05/2007 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.
1. Replace missing FDC inlet cover, on first floor, in Disney loading area.
2. Replace missing FDC inlet cover, on first floor, by Chick-fil-A.