Case: T07FR00008
Case Details
Entered Date:
01/02/2007
Applicant:
BROADWAY POWER CENTER GROUP LLC
Description:
Full FPI completed 1/2/07
Outstanding Inspections
Case Number: T07FR00008
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/02/2007 | INSP - FULL | DGREENLE | Correction Required | Please correct the following Tucson Fire Code violations: ___ A record of the sprinkler system inspections shall be made available prior to approval. |
01/02/2007 | VIOL - PRECAUTION AGAINST FIRE | DGREENLE | Correction Required | TFC 315.2.1 - Sprinkler head clearance. Storage shall be maintained 24 inches (610 mm) or more below the ceiling in non-sprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. ___ Remove storage to 18 inches or more below sprinkler head. |
01/02/2007 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Correction Required | TFC 605.3 - Blocked Electrical Panel. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. ___ Clear area in front of electrical panel, rear stock room, next to bathroom |
01/02/2007 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Correction Required | TFC 605.4 - Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. ___ Do not "daisy-chain" approved circuit protected extension cords, front display area |
01/02/2007 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Correction Required | TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. ___ Remove extension cord and/or replace with approved permanent electrical power source, copy machine ___ Remove extension cord and/or replace with approved permanent electrical power source, front door opener |
01/02/2007 | VIOL - FIRE RESIST.RATED CONST | DGREENLE | Correction Required | TFC 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. ___ Replace missing ceiling tile, over front door |
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00008
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/18/2007 | INSP - REINSPECTION | DGREENLE | Approved | Full compliance upon re-inspection 1/17/07 |