Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T07FR00008
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/02/2007 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | TFC 605.3 - Blocked Electrical Panel. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. ___ Clear area in front of electrical panel, rear stock room, next to bathroom |
|
01/02/2007 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. ___ Remove extension cord and/or replace with approved permanent electrical power source, copy machine ___ Remove extension cord and/or replace with approved permanent electrical power source, front door opener |
|
01/02/2007 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | TFC 605.4 - Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. ___ Do not "daisy-chain" approved circuit protected extension cords, front display area |