Case: T07FR00003
Case Details
Entered Date:
01/02/2007
Applicant:
CT PROPERTIES LLC
Description:
full inspection
Completed Inspections
Case Status: COMPLETE
Case Number: T07FR00003
Case Description: INSPECTION
Total Completed Inspections - 10
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/17/2006 | VIOL - FIRE PROTECTION SYSTEMS | DRAMIREZ | Approved | TFC 912.3 Shall provide a minimum of 3 feet clearance around the automatic sprinkler riser. |
08/17/2006 | INSP - LIFE SAFETY | DRAMIREZ | Approved | TFC 605.1 Electrical panels located at SE corner of the building shal be protected from possible impact by vehicle. This creates an electrical hazard. |
08/17/2006 | INSP - LIFE SAFETY | DRAMIREZ | Approved | TFC 605.4 Power taps shall be directly connected to permanently installed recepticals. |
08/17/2006 | INSP - LIFE SAFETY | DRAMIREZ | Approved | TFC 605.6 Approved covers shall be provided for all switch and electrical outlet boxes. |
08/17/2006 | VIOL - PRECAUTION AGAINST FIRE | DRAMIREZ | Approved | TFC 312.1 Vehical protection shall be provided for the electrical equipment located to the NW corner of the building. |
08/17/2006 | VIOL - PRECAUTION AGAINST FIRE | DRAMIREZ | Approved | TFC 304.3.1 Oily rags shall be stored in a listed disposable container |
08/17/2006 | VIOL - PRECAUTION AGAINST FIRE | DRAMIREZ | Approved | TFC 315.2.1 Storage shall be maintained 2 feet or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches in sprinklered areas. |
08/30/2006 | VIOL - MEANS OF EGRESS | DRAMIREZ | Approved | TFC 1011.1 Access tyo exits shall be marked by readily visable exit signs in cases where the exit or pass of egress travel is not immediately visable. You shall provide an exit sign in the shop area directing to the location of the east wall. |
08/30/2006 | VIOL - MEANS OF EGRESS | DRAMIREZ | Approved | BODY SHOP TFC 1006.1 Means of egress shall be illuminated at all times |
08/30/2006 | INSP - FULL | DRAMIREZ | Approved | Number 1 of 5 inspections conducted at this location. 5 buildings, 5 seperate T0 numbers. Buildings and T0 numbers are as follows: 1.) Body Shop Bldg. T07FR00003 2.) Parts Bulk Storage Bldg. T07FR00004 3.) Detail Area and Paint Shop Bldg. T07FR00005 4.) Used Vehicle Reconditioning Repair Bldg. T07FR00006 5.) Service Bay Bldg. T07FR00007 |