Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

01/02/2007

Applicant:

CT PROPERTIES LLC

Description:

full inspection

Completed Inspections

Case Status: COMPLETE
Case Number: T07FR00003
Case Description: INSPECTION
Total Completed Inspections - 10
End Date Description Inspector Results Comments
08/17/2006 VIOL - FIRE PROTECTION SYSTEMS DRAMIREZ Approved TFC 912.3 Shall provide a minimum of 3 feet clearance around the automatic sprinkler riser.
08/17/2006 INSP - LIFE SAFETY DRAMIREZ Approved TFC 605.1 Electrical panels located at SE corner of the building shal be protected from possible impact by vehicle. This creates an electrical hazard.
08/17/2006 INSP - LIFE SAFETY DRAMIREZ Approved TFC 605.4 Power taps shall be directly connected to permanently installed recepticals.
08/17/2006 INSP - LIFE SAFETY DRAMIREZ Approved TFC 605.6 Approved covers shall be provided for all switch and electrical outlet boxes.
08/17/2006 VIOL - PRECAUTION AGAINST FIRE DRAMIREZ Approved TFC 312.1 Vehical protection shall be provided for the electrical equipment located to the NW corner of the building.
08/17/2006 VIOL - PRECAUTION AGAINST FIRE DRAMIREZ Approved TFC 304.3.1 Oily rags shall be stored in a listed disposable container
08/17/2006 VIOL - PRECAUTION AGAINST FIRE DRAMIREZ Approved TFC 315.2.1 Storage shall be maintained 2 feet or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches in sprinklered areas.
08/30/2006 VIOL - MEANS OF EGRESS DRAMIREZ Approved TFC 1011.1 Access tyo exits shall be marked by readily visable exit signs in cases where the exit or pass of egress travel is not immediately visable. You shall provide an exit sign in the shop area directing to the location of the east wall.
08/30/2006 VIOL - MEANS OF EGRESS DRAMIREZ Approved BODY SHOP TFC 1006.1 Means of egress shall be illuminated at all times
08/30/2006 INSP - FULL DRAMIREZ Approved Number 1 of 5 inspections conducted at this location. 5 buildings, 5 seperate T0 numbers. Buildings and T0 numbers are as follows: 1.) Body Shop Bldg. T07FR00003 2.) Parts Bulk Storage Bldg. T07FR00004 3.) Detail Area and Paint Shop Bldg. T07FR00005 4.) Used Vehicle Reconditioning Repair Bldg. T07FR00006 5.) Service Bay Bldg. T07FR00007