Inspection Status: Approved
Inspection History: VIOL - PRECAUTION AGAINST FIRE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/17/2006 |
VIOL - PRECAUTION AGAINST FIRE |
|
Approved |
TFC 315.2.1 Storage shall be maintained 2 feet or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches in sprinklered areas. |
| 08/17/2006 |
VIOL - PRECAUTION AGAINST FIRE |
|
Approved |
TFC 304.3.1 Oily rags shall be stored in a listed disposable container |
| 08/17/2006 |
VIOL - PRECAUTION AGAINST FIRE |
|
Approved |
TFC 312.1 Vehical protection shall be provided for the electrical equipment located to the NW corner of the building. |