Description:

CHILLER SYSTEM NOT WORKING, DOES NOT WANT THE HEAT ON, VENTS BROKEN, FAN ON CHILLER SYSTEM NOT BLOWING OUT, AIR IS COLD. VENTING IS DIRTY. 2A GTI-SM/01/10/07

Outstanding Inspections

Case Number: T07DV00075
Case Status: COMPLIAN
Case Description: RES: MINIMUM HOUSING
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
VIOL(PL) - FIXTURES None Not Inspected
NPO(HC)-COOLING None Not Inspected
NPO(HC)-HEATING & VENTILATION None Not Inspected
01/12/2007 INSP - INITIAL CODE ENFORCMENT RMENDOZA Violation AIR INTAKE HAS IMPROPER FILTER INSTALLED. REMOVED FILTER AND NOTICED DUCTS HAVE AN ACCUMULATION OF DUST AND LINT. THERMOSTAT IS NOT WORKING AS INTENDED. FAN FOR AC/HEAT WILL NOT TURN OFF. BATHROOM SHOWER HEAD/SPOUT VALVE DOES NOT WORK PROPERLY. SMALL HOLES IN WINDOW FRAMES FROM SHUTTER REPLACEMENT.RM

Completed Inspections

Case Status: COMPLIAN
Case Number: T07DV00075
Case Description: RES: MINIMUM HOUSING
Total Completed Inspections - 1
End Date Description Inspector Results Comments
02/05/2007 INSP - FOLLOW UP CODE ENFORCE RMENDOZA Approved DUCTS APPEAR TO HAVE BEEN CLEANED. THERMOSTAT HAS BEEN REPLACED AND IS WORKING PROPERLY. CHILLER SET TO COOL. COOL AIR COMING OUT OF ALL VENTS IN THE UNIT. BATHROOM FAUCET IS NOW WORKING PROPERLY. AIR INTAKE VENT IS BROKEN AND WRONG FILTER STILL INSTALLED. MAINTENANCE REPAIRED. BATHROOM AND KITCHEN VENTS WORKING BUT ARE MISSING OPEN/CLOSE LEVER. NO VIOLATION. FRONT DOOR MOLDING HAS SMALL CRACK. MAINTENANCE TO REPAIR AS NEEDED. NO VIOLATION. KITCHEN TILE AND BASEBOARD APPEAR TO HAVE PULLED UP SLIGHTLY. TENANT STATED CONCERNED ABOUT MOLD. NO MOLD VISIBLE ON OR AROUND WALL AND TILE AREA WHERE TILE AND BASEBOARD ARE PULLED UP. (NON DNR ISSUE) MAINTENANCE STATED WILL REPAIR TILE AND BASEBOARD WITHIN 1 DAY. NO VIOLATION. CASE CLOSED AT THIS TIME. RM

Completed Activity Special Conditions

Case Description - RES: MINIMUM HOUSING
Case Number - T07DV00075
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 2
Date Name
01/16/2007 NOTICE OF VIOLATION ISSUED
03/23/2007 VIOLATION CLOSED