Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

12/29/2006

Applicant:

KARABELAS DIMITRI C

Description:

Full inspection

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR02959
Case Description: INSPECTION
Total Completed Inspections - 13
End Date Description Inspector Results Comments
04/06/2006 VIOL - MEANS OF EGRESS DRAMIREZ Approved TFC 1027.2 Exits shall be continuously maintained from obstructions and impediments. Screen door to the rear exit binds against the floor when opening.
04/06/2006 VIOL - MEANS OF EGRESS DRAMIREZ Approved TFC 1008.1.8.4 Manually operated flush bolts or surface bolts shall not be permitted. (rear exit door)
04/06/2006 VIOL - FIRE PROTECTION SYSTEMS DRAMIREZ Approved TFC 904.11.1 Pull station for hood system shall be relocated to a location with a minimum of 10 ft. and a max. of 30 ft. travel distance from cooking appliances. Must be in the direction of the exit.
04/06/2006 VIOL - FIRE PROTECTION SYSTEMS DRAMIREZ Approved TFC 3003.3 Compressed gas cylindersshall be secured against accidental dislodgement.
04/06/2006 VIOL - FIRE PROTECTION SYSTEMS DRAMIREZ Approved TFC904.11.5 Portable fire extinguihsers shall be provided within 30 feet travel distance of cooking equipment.
04/06/2006 VIOL - FIRE PROTECTION SYSTEMS DRAMIREZ Approved TFC 904.4 Commercial hood system shall be inspected and tested at 6 mo. intervals. Your system is past due for inspection.
04/06/2006 VIOL - FIRE PROTECTION SYSTEMS DRAMIREZ Approved TFC Portable fire extinguishers shall be installed in a hanger or braket.
04/06/2006 VIOL - FIRE PROTECTION SYSTEMS DRAMIREZ Approved TFC 906.6 Portable extingguishers shall not be obstructed from view.
04/06/2006 VIOL - BUILDING SVCS & SYSTEMS DRAMIREZ Approved TFC 605.5 Extension cords shall not be a substitute for permanent wiring.
04/06/2006 VIOL - FIRE SERVICE FEATURES DRAMIREZ Approved TFC 505.1 You shall provide address numbers for the building. Numbers shall be legible and visable from the street.
04/06/2006 VIOL - FIRE SERVICE FEATURES DRAMIREZ Approved TFC 605.3 Working space and clearance shall be provided for the electric service panel. Minimum of 36 inches.
04/06/2006 VIOL - FIRE SERVICE FEATURES DRAMIREZ Approved TFC 504.2 Exterior doors rendered nonfunctional and that retain a functional appearance Shall have affixed to the exterior side of the door a sign reading "THIS DOOR BLOCKED".
04/06/2006 INSP - FULL DRAMIREZ Approved