Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T06FR02959

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
04/06/2006 VIOL - FIRE PROTECTION SYSTEMS Approved TFC 906.6 Portable extingguishers shall not be obstructed from view.
04/06/2006 VIOL - FIRE PROTECTION SYSTEMS Approved TFC Portable fire extinguishers shall be installed in a hanger or braket.
04/06/2006 VIOL - FIRE PROTECTION SYSTEMS Approved TFC 904.4 Commercial hood system shall be inspected and tested at 6 mo. intervals. Your system is past due for inspection.
04/06/2006 VIOL - FIRE PROTECTION SYSTEMS Approved TFC904.11.5 Portable fire extinguihsers shall be provided within 30 feet travel distance of cooking equipment.
04/06/2006 VIOL - FIRE PROTECTION SYSTEMS Approved TFC 3003.3 Compressed gas cylindersshall be secured against accidental dislodgement.
04/06/2006 VIOL - FIRE PROTECTION SYSTEMS Approved TFC 904.11.1 Pull station for hood system shall be relocated to a location with a minimum of 10 ft. and a max. of 30 ft. travel distance from cooking appliances. Must be in the direction of the exit.