Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T06FR02959
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/06/2006 | VIOL - FIRE PROTECTION SYSTEMS | Approved | TFC 906.6 Portable extingguishers shall not be obstructed from view. | |
| 04/06/2006 | VIOL - FIRE PROTECTION SYSTEMS | Approved | TFC Portable fire extinguishers shall be installed in a hanger or braket. | |
| 04/06/2006 | VIOL - FIRE PROTECTION SYSTEMS | Approved | TFC 904.4 Commercial hood system shall be inspected and tested at 6 mo. intervals. Your system is past due for inspection. | |
| 04/06/2006 | VIOL - FIRE PROTECTION SYSTEMS | Approved | TFC904.11.5 Portable fire extinguihsers shall be provided within 30 feet travel distance of cooking equipment. | |
| 04/06/2006 | VIOL - FIRE PROTECTION SYSTEMS | Approved | TFC 3003.3 Compressed gas cylindersshall be secured against accidental dislodgement. | |
| 04/06/2006 | VIOL - FIRE PROTECTION SYSTEMS | Approved | TFC 904.11.1 Pull station for hood system shall be relocated to a location with a minimum of 10 ft. and a max. of 30 ft. travel distance from cooking appliances. Must be in the direction of the exit. |