Case: T06FR02938
Case Details
Entered Date:
12/28/2006
Applicant:
DND NEFFSON CO
Description:
Full Fire Inspection Done By Inspector John Bieg, on 12-28-06.
Outstanding Inspections
Case Number: T06FR02938
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 10
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/28/2006 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | TFC 315.2.1 Ceiling clearance. Storage shall be maintained 24 inches (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. 1. Remove storage to 18 inches or more below sprinkler head in optical storage closet. |
| 12/28/2006 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 508.5.4 Obstruction. Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, fire department inlet connections or fire protection system control valves in a manner that would prevent such equipment or fire hydrants from being immediately discernible. 1. Remove bushes from obstructing fire department connections on west side of building. |
| 12/28/2006 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. 1. Place an approved "blank" in the space of upstairs electrical panels. 2. Repair electric wiring in an approved manner. {freyed wiring for overhead lamp in south side of recieving dock}. |
| 12/28/2006 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. 1. Remove storage from blocking bailer electric panel. |
| 12/28/2006 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. 1. Remove extension cord in downstairs display room. 2. Remove extension cord by recieving dock west roll up door {upstairs}. 3. Remove all extension cords used for lighting in semi trailer storage room. |
| 12/28/2006 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. 1. Replace cover on electrical box, in downstairs shoe stock room {overhead}. 2. Replace communications outlet cover in computer room. 3. Replace outlet covers on the east wall of the computer room. |
| 12/28/2006 | VIOL - FIRE RESIST.RATED CONST | JBURGE | Correction Required | TFC 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. 1. Repair hole in wall on lower level exit corridor, near the dresses department. 2. Repair hole in wall, in lower level shoe stock room. 3. Repair hole in wall, in downstairs computer room. 4. Replace ceiling tiles, in downstairs computer room. 5. Repair hole in wall, south end of cmputer room. 6. Replace ceiling tile, in jewlry box room. |
| 12/28/2006 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1011.2 Illumination. Exit signs shall be internally or externally illuminated. 1. Exit sign in lower level shoe stock room shall be illuminated. |
| 12/28/2006 | VIOL - COMPRESSED GASES | JBURGE | Correction Required | TFC 3003.3.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. 1. Secure helium container in an approved manner, in downstairs display room. |
| 12/29/2006 | VIOL - ADMINISTRATION | JBURGE | Correction Required | TFC 102.4 Application of building code. The design and construction of new structures shall comply with the International Building Code. Repairs, alterations and additions to existing structures shall comply with the Internationsl Building Code or New Jersey Rehabilitation Subcode. 1. IBC 507.3 The area of a 2 story M is not limited if it is sprinklered and surrounded by 60 foot yards. Remove simi trailer from recieving dock, or submit plans to install an approved fire protection system. |
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR02938
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/28/2006 | INSP - FULL | JBURGE | Approved | Please correct the following Tucson Fire Code violations: |