Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T06FR02938
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Correction Required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/28/2006 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. 1. Replace cover on electrical box, in downstairs shoe stock room {overhead}. 2. Replace communications outlet cover in computer room. 3. Replace outlet covers on the east wall of the computer room. |
|
| 12/28/2006 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. 1. Remove extension cord in downstairs display room. 2. Remove extension cord by recieving dock west roll up door {upstairs}. 3. Remove all extension cords used for lighting in semi trailer storage room. |
|
| 12/28/2006 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. 1. Remove storage from blocking bailer electric panel. |
|
| 12/28/2006 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. 1. Place an approved "blank" in the space of upstairs electrical panels. 2. Repair electric wiring in an approved manner. {freyed wiring for overhead lamp in south side of recieving dock}. |