Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

12/21/2006

Applicant:

MENLO PARK SHOPPING CENTER COMPANY

Description:

Full Inspection

Outstanding Inspections

Case Number: T06FR02922
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 28
End Date Description Inspector Results Comments
12/21/2006 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1008.1.8 - remove 2x4 lock mechanism and associated hardware from door of small room east of stage
12/21/2006 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1008.1.8.4 - remove manually operated surface bolt locks ballrooms, east exits
12/21/2006 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1008.8 - remove padlock and slide bolt locks from door, small room, west of stage
12/21/2006 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 - repair exit sign, kitchen, east side
12/21/2006 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 - repair exit sign, kitchen, west side, at doorway leading to lobby
12/21/2006 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 - repair exit sign, tower, ground floor, NE exit
12/21/2006 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 - repair exit sign, tower, ground floor, SW corner
12/21/2006 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.5 - repair emergency light, Buckley room, west side
12/21/2006 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.5 - repair emergency light, Gold room, east side
12/21/2006 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.5 - repair emergency light, service hallway, east side of kitchen, NE exit
12/21/2006 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.2 - remove storage from path of egress and from around electrical panel, small room, east of stage
12/28/2006 VIOL - FIRE SERVICE FEATURES TKNAPP Correction Required 506.1 - Repair/replace Fire Dept key box for elevator, tower, ground floor
12/28/2006 VIOL - FIRE SERVICE FEATURES TKNAPP Correction Required 508.5.4 - Remove storage from sprinkler riser room. Keep controls accessible.
12/28/2006 VIOL - FIRE SERVICE FEATURES TKNAPP Correction Required 510.1 - Improve visibility of signage for riser room
12/28/2006 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.1 - repair/replace electrical conduit that has been crushed, outside boiler room, northeast corner
12/28/2006 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.1 - repair/replace light fixture so bulb is not hanging by power wire, small hallway from kitchen to lobby entrance of bar
12/28/2006 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.1 - replace missing electrical panel covers, east side equipment room, east and north walls
12/28/2006 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.1 - secure electrical switch box to to building, east side of building, near trash compactor
12/28/2006 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.3 - remove storage to provide 3-foot clearance in front of entire width of electrical switch panels, boiler room
12/28/2006 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.3 - remove storage to provide 3-foot clearance in front of entire width of electrical switch panels, laundry room
12/28/2006 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.4 - remove/replace multi-plug adapter with circuit-protected one, neon sign, southwest corner of bar
12/28/2006 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.6 - cover open electrical junction box, tower, 2nd floor, northeast end, storage room
12/28/2006 VIOL - FIRE RESIST.RATED CONST TKNAPP Correction Required 703.1 - repair hole in ceiling, boiler room
12/28/2006 VIOL - FIRE RESIST.RATED CONST TKNAPP Correction Required 703.1 - repair hole in ceiling, kitchen, above oven
12/28/2006 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 901.4.4 - replace fire extinguisher, missing from cabinet near room 335
12/28/2006 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 901.6 - have fire extinguisher inspected and tagged, near room 188
12/28/2006 VIOL - FIRE PROTECTION SYSTEMS TKNAPP Correction Required 901.6 - have fire extinguisher inspected and tagged, near room 273
12/28/2006 VIOL - COMPRESSED GASES TKNAPP Correction Required 3003.3 - secure CO2 cylinders, west side of kitchen

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR02922
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/21/2006 INSP - FULL TKNAPP Approved Full FPI performed 12/4/06