Case: T06FR02922
Case Details
Entered Date:
12/21/2006
Applicant:
MENLO PARK SHOPPING CENTER COMPANY
Description:
Full Inspection
Outstanding Inspections
Case Number: T06FR02922
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 28
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/21/2006 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.8 - remove 2x4 lock mechanism and associated hardware from door of small room east of stage |
12/21/2006 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.1.8.4 - remove manually operated surface bolt locks ballrooms, east exits |
12/21/2006 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1008.8 - remove padlock and slide bolt locks from door, small room, west of stage |
12/21/2006 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.3 - repair exit sign, kitchen, east side |
12/21/2006 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.3 - repair exit sign, kitchen, west side, at doorway leading to lobby |
12/21/2006 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.3 - repair exit sign, tower, ground floor, NE exit |
12/21/2006 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.3 - repair exit sign, tower, ground floor, SW corner |
12/21/2006 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.5 - repair emergency light, Buckley room, west side |
12/21/2006 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.5 - repair emergency light, Gold room, east side |
12/21/2006 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1026.5 - repair emergency light, service hallway, east side of kitchen, NE exit |
12/21/2006 | VIOL - MEANS OF EGRESS | TKNAPP | Correction Required | 1027.2 - remove storage from path of egress and from around electrical panel, small room, east of stage |
12/28/2006 | VIOL - FIRE SERVICE FEATURES | TKNAPP | Correction Required | 506.1 - Repair/replace Fire Dept key box for elevator, tower, ground floor |
12/28/2006 | VIOL - FIRE SERVICE FEATURES | TKNAPP | Correction Required | 508.5.4 - Remove storage from sprinkler riser room. Keep controls accessible. |
12/28/2006 | VIOL - FIRE SERVICE FEATURES | TKNAPP | Correction Required | 510.1 - Improve visibility of signage for riser room |
12/28/2006 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.1 - repair/replace electrical conduit that has been crushed, outside boiler room, northeast corner |
12/28/2006 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.1 - repair/replace light fixture so bulb is not hanging by power wire, small hallway from kitchen to lobby entrance of bar |
12/28/2006 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.1 - replace missing electrical panel covers, east side equipment room, east and north walls |
12/28/2006 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.1 - secure electrical switch box to to building, east side of building, near trash compactor |
12/28/2006 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.3 - remove storage to provide 3-foot clearance in front of entire width of electrical switch panels, boiler room |
12/28/2006 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.3 - remove storage to provide 3-foot clearance in front of entire width of electrical switch panels, laundry room |
12/28/2006 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.4 - remove/replace multi-plug adapter with circuit-protected one, neon sign, southwest corner of bar |
12/28/2006 | VIOL - BUILDING SVCS & SYSTEMS | TKNAPP | Correction Required | 605.6 - cover open electrical junction box, tower, 2nd floor, northeast end, storage room |
12/28/2006 | VIOL - FIRE RESIST.RATED CONST | TKNAPP | Correction Required | 703.1 - repair hole in ceiling, boiler room |
12/28/2006 | VIOL - FIRE RESIST.RATED CONST | TKNAPP | Correction Required | 703.1 - repair hole in ceiling, kitchen, above oven |
12/28/2006 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.4.4 - replace fire extinguisher, missing from cabinet near room 335 |
12/28/2006 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6 - have fire extinguisher inspected and tagged, near room 188 |
12/28/2006 | VIOL - FIRE PROTECTION SYSTEMS | TKNAPP | Correction Required | 901.6 - have fire extinguisher inspected and tagged, near room 273 |
12/28/2006 | VIOL - COMPRESSED GASES | TKNAPP | Correction Required | 3003.3 - secure CO2 cylinders, west side of kitchen |
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR02922
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/21/2006 | INSP - FULL | TKNAPP | Approved | Full FPI performed 12/4/06 |