Case: T06FR02922

Parcel: 11618432G


Addresses:

475 N GRANADA AV

Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
12/28/2006 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.1 - replace missing electrical panel covers, east side equipment room, east and north walls
12/28/2006 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.1 - secure electrical switch box to to building, east side of building, near trash compactor
12/28/2006 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.1 - repair/replace light fixture so bulb is not hanging by power wire, small hallway from kitchen to lobby entrance of bar
12/28/2006 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.4 - remove/replace multi-plug adapter with circuit-protected one, neon sign, southwest corner of bar
12/28/2006 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.6 - cover open electrical junction box, tower, 2nd floor, northeast end, storage room
12/28/2006 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.3 - remove storage to provide 3-foot clearance in front of entire width of electrical switch panels, laundry room
12/28/2006 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.1 - repair/replace electrical conduit that has been crushed, outside boiler room, northeast corner
12/28/2006 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.3 - remove storage to provide 3-foot clearance in front of entire width of electrical switch panels, boiler room