Case Details

Status:

FIELD

Type:

INSPECTION

Entered Date:

12/20/2006

Applicant:

FOOTHILLS BUSINESS VENTURES LLC 90% &

Description:

Full Fire Inspection

Outstanding Inspections

Case Number: T06FR02918
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
12/21/2006 VIOL - BUILDING SVCS & SYSTEMS NSPRENGE Violation 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. Remove stock located under electrical panel.
12/21/2006 VIOL - FIRE RESIST.RATED CONST NSPRENGE Violation 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Replace the missing ceiling tiles over your back stock room area.
12/21/2006 VIOL - MEANS OF EGRESS NSPRENGE Violation 1003.6 Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel. Remove shelves, trash, and ladder, and stock blocking the exit path to the door.
12/21/2006 VIOL - MEANS OF EGRESS NSPRENGE Violation 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Replace key locking cylinder on egress side of rear exit door with a thumb bolt latch.
12/21/2006 VIOL - MEANS OF EGRESS NSPRENGE Violation 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25mm)high on a contrasting background. Replace old sign over front door with the required sign.
12/21/2006 VIOL - MEANS OF EGRESS NSPRENGE Violation 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. Remove slide bolt lock from rear exit door.
12/21/2006 VIOL - MEANS OF EGRESS NSPRENGE Violation 1011.2 Illumination. Exit signs shall be internally or externally illuminated. Provide constant illumination for front and rear exit signs.