Case: T06FR02918

Parcel: 137105050


Addresses:

5550 S 12TH AV #180


Inspection Status: Violation

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T06FR02918

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Violation

Date Description Inspector Results Comments
12/21/2006 VIOL - MEANS OF EGRESS Violation 1008.1.8 Door operations. Except as specifically permitted
by this section egress doors shall be readily openable from
the egress side without the use of a key or special knowledge
or effort. Replace key locking cylinder on egress side of rear exit door with a thumb bolt latch.
12/21/2006 VIOL - MEANS OF EGRESS Violation 1008.1.8.3 Locks and latches. Locks and latches shall
be permitted to prevent operation of doors where any of
the following exists:
2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED
WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch
(25mm)high on a contrasting background. Replace old sign over front door with the required sign.
12/21/2006 VIOL - MEANS OF EGRESS Violation 1008.1.8.4 Bolt locks. Manually operated flush bolts or
surface bolts are not permitted. Remove slide bolt lock from rear exit door.
12/21/2006 VIOL - MEANS OF EGRESS Violation 1011.2 Illumination. Exit signs shall be internally or externally
illuminated. Provide constant illumination for front and rear exit signs.
12/21/2006 VIOL - MEANS OF EGRESS Violation 1003.6 Means of egress continuity. The path of egress travel
along a means of egress shall not be interrupted by any building
element other than a means of egress component as specified in
this chapter. Obstructions shall not be placed in the required
width of a means of egress except projections permitted by this
chapter. The required capacity of a means of egress system
shall not be diminished along the path of egress travel. Remove shelves, trash, and ladder, and stock blocking the exit path to the door.