Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

12/20/2006

Applicant:

RANDOLPH PLAZA II LLC

Description:

Full Inspection

Outstanding Inspections

Case Number: T06FR02917
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
12/22/2006 INSP - FULL BCORRALE Correction Required Please correct the following Tucson Fire Code violations. Code references are from the International Fire Code 2003 Edition with modifications.

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR02917
Case Description: INSPECTION
Total Completed Inspections - 7
End Date Description Inspector Results Comments
12/22/2006 VIOL - COMPRESSED GASES BCORRALE Approved 7. Helium cylinders not secured. 3003.3.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. Securing of compressed gas containers, cylinders and tanks shall be by one of the following methods: Securing containers, cylinders and tanks to a fixed object with one or more restraints.
12/22/2006 VIOL - HIGH PILED COMBUSTIBLES BCORRALE Approved 6. Rear stockroom housekeeping, aisle width. 2305.4 Aisle maintenance. Aisles shall be kept clear of storage, waste material and debris. Fire department access doors, aisles and exit doors shall not be obstructed. During restocking operations using manual stocking methods, a minimum unobstructed aisle width of 24 inches (610 mm) shall be maintained.
12/22/2006 VIOL - FIRE RESIST.RATED CONST BCORRALE Approved 5. Ceiling tiles missing. 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire.
12/22/2006 VIOL - PRECAUTION AGAINST FIRE BCORRALE Approved 4. Combustible storage directly in front of electrical outlet. 315.2 Storage in buildings. Storage of combustible materials in buildings shall be orderly. Storage shall be separated from heaters or heating devices by distance or shielding so that ignition cannot occur.
12/22/2006 VIOL - PRECAUTION AGAINST FIRE BCORRALE Approved 3. Storage of stock in storage room mezzanine too close to sprinkler heads. 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings.
12/22/2006 VIOL - BUILDING SVCS & SYSTEMS BCORRALE Approved 2. Faceplate missing on electrical outlet by ice cream machine. 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
12/22/2006 VIOL - BUILDING SVCS & SYSTEMS BCORRALE Approved 1. Stockroom electrical panel blocked by shelving on floor. 605.3 Working spaces. The working space shall not be less than the width of the electrical service equipment. No storage of any materials shall be located within the designated working space.