Case: T06FR02917

Parcel: 130140260


Addresses:

4122 E 22ND ST


Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T06FR02917

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
01/05/2007 VIOL - BUILDING SVCS & SYSTEMS Approved Stockroom electrical panel clear of obstructions. Clear path to panel, appropriate work space.
01/05/2007 VIOL - BUILDING SVCS & SYSTEMS Approved Faceplate replaced.
12/22/2006 VIOL - BUILDING SVCS & SYSTEMS Violation 1. Stockroom electrical panel blocked by shelving on floor.
605.3 Working spaces. The working space shall not be less than the width of the electrical service equipment. No storage of any materials shall be located within the designated working space.
12/22/2006 VIOL - BUILDING SVCS & SYSTEMS Violation 2. Faceplate missing on electrical outlet by ice cream machine.
605.6 Unapproved conditions. Open junction boxes and
open-wiring splices shall be prohibited. Approved covers shall
be provided for all switch and electrical outlet boxes.