Description:

Full Fire Prevention Inspection

Outstanding Inspections

Case Number: T06FR02892
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
12/15/2006 VIOL - PRECAUTION AGAINST FIRE DGREENLE Correction Required Clearance below sprinklers: TFC 315.2.1 Ceiling clearance. Storage shall be maintained a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. ***Remove storage to 18 inches or more below sprinkler head in VM office.
12/15/2006 VIOL - MEANS OF EGRESS DGREENLE Correction Required Egress Maintenance 1027.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency. ***clear paths of egress shall be maintained in rear stocking area. ***clear path of egress shall be maintained in VM office.

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR02892
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/15/2006 INSP - FULL DGREENLE Approved The property is in exemplary condition. Your commitment to fire safety is appreciated. These are ideas we discussed for further consideration. ***Periodically test your emergency lighting fixtures that were inaccessible during our inspection. Keep a record of these tests. ***Replace the sign on the back door that is falling apart. Indicate that the sprinkler riser is located inside the door and to the left. ***Hang signs away from and 18" below sprinkler heads and keep them in line with the spray (not perpendicular).