Case: T06FR02890
Case Details
Entered Date:
12/14/2006
Applicant:
K-GAM SAGUARO PROP LLC 1/2 & SEA COLONY
Description:
Full inspection done by Inspector John Bieg. Occupancy type "M". Property rep Sandy Hill.
Outstanding Inspections
Case Number: T06FR02890
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 9
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/14/2006 | INSP - FULL | JBURGE | Correction Required | Please correct the following Tucson Fire Code violations: All violations have been corrected. 1-4-07. |
12/15/2006 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | 315.2.3 Equipment rooms. Combustible material shall not be stored in boiler rooms, mechanical rooms or electrical equipment rooms. ***No storage in electrical room. |
12/15/2006 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | 315.3.1 Storage beneath overhead projections from buildings. Combustible materials stored or displayed outside of buildings that are protected by automatic sprinklers shall not be stored or displayed under nonsprinklered eaves, canopies or other projections or overhangs. ***Furniture shall not be stored under east side overhang,{outside}. |
12/15/2006 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | 508.5.4 Obstruction. Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, fire department inlet connections or fire protection system control valves in a manner thatwould prevent such equipment or fire hydrants from being immediately discernible. The fire department shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants. ***Clear storage from sprinkler system riser. |
12/15/2006 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. ***Electrical shall not be blocked. |
12/15/2006 | VIOL - FIRE RESIST.RATED CONST | JBURGE | Correction Required | 703.2 Opening protectives. Opening protectives shall be maintained in an operative condition in accordance with NFPA 80. Fire doors and smoke barrier doors shall not be blocked or obstructed or otherwise made inoperable. Fusible links shall be replaced promptly whenever fused or damaged. Fire door assemblies shall not be modified. ***Don't prop open fire doors. |
12/15/2006 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ***Extinguisher at south east door needs annual inspection. ***Building sprinkler system shsll be tested annually. |
12/15/2006 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | 1026.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress. ***Emergency lighting in the stock room at the east door shall be repaired. |
12/15/2006 | VIOL - HIGH PILED COMBUSTIBLES | JBURGE | Correction Required | 2305.4 Aisle maintenance. When restocking is not being conducted, aisles shall be kept clear of storage, waste material and debris. Fire department access doors, aisles and exit doors shall not be obstructed. During restocking operations using manual stocking methods, a minimum unobstructed aisle width of 24 inches (610 mm) shall be maintained in 48-inch (1219 mm) or smaller aisles, and a minimum unobstructed aisle width of one-half of the required aisle width shall be maintained in aisles greater than 48 inches (1219 mm). During mechanical stocking operations, a minimum unobstructed aisle width of 44 inches (1118 mm) shall be maintained in accordance with Section 2306.9. ***Isles must have half of total width clear during restocking. |