Inspection Status: Correction Required
Inspection History: VIOL - HIGH PILED COMBUSTIBLES
Case Number - T06FR02890
Inspection Description - VIOL - HIGH PILED COMBUSTIBLES
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/15/2006 | VIOL - HIGH PILED COMBUSTIBLES | Correction Required | 2305.4 Aisle maintenance. When restocking is not being conducted, aisles shall be kept clear of storage, waste material and debris. Fire department access doors, aisles and exit doors shall not be obstructed. During restocking operations using manual stocking methods, a minimum unobstructed aisle width of 24 inches (610 mm) shall be maintained in 48-inch (1219 mm) or smaller aisles, and a minimum unobstructed aisle width of one-half of the required aisle width shall be maintained in aisles greater than 48 inches (1219 mm). During mechanical stocking operations, a minimum unobstructed aisle width of 44 inches (1118 mm) shall be maintained in accordance with Section 2306.9. ***Isles must have half of total width clear during restocking. |