Case Details

Status:

COMPLETE

Type:

COMPLAINT (RESIDENTIAL)
Address:

Entered Date:

12/13/2006

Applicant:

CAROLINA LEASING LIMITED PRTNRSHP 80% &

Description:

access issue.

Outstanding Inspections

Case Number: T06FR02878
Case Status: COMPLETE
Case Description: COMPLAINT (RESIDENTIAL)
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
12/13/2006 INSP - FULL RDUARTE Correction Required access issue, e mail from Captain Pena.

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR02878
Case Description: COMPLAINT (RESIDENTIAL)
Total Completed Inspections - 1
End Date Description Inspector Results Comments
12/18/2006 COMPL - INITIAL INSPECTION DRAMIREZ Approved Engine crew responded to a medical call at this location. They had a difficult time passing through the front gate because it was to narrow. Engine Capt. requested Fire Prevention to investigate. Fire code requires a property to provide one access point with a width of 20ft.and a heigth of 15ft. The front gate does not meet these requierments but two other access point are provided for the property that do meet the requierments.They are located to the west of the complex and to the SW. They are provided with FD pad locks. We can request, suggest or recommend that they extend the opening for the front gate for a better, quicker and safer access into the property but because of the two other entry points, they are not requiered to.