Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: COMPL - INITIAL INSPECTION
Case Number - T06FR02878
Inspection Description - COMPL - INITIAL INSPECTION
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/18/2006 | COMPL - INITIAL INSPECTION | Approved | Engine crew responded to a medical call at this location. They had a difficult time passing through the front gate because it was to narrow. Engine Capt. requested Fire Prevention to investigate. Fire code requires a property to provide one access point with a width of 20ft.and a heigth of 15ft. The front gate does not meet these requierments but two other access point are provided for the property that do meet the requierments.They are located to the west of the complex and to the SW. They are provided with FD pad locks. We can request, suggest or recommend that they extend the opening for the front gate for a better, quicker and safer access into the property but because of the two other entry points, they are not requiered to. |