Case: T06FR02838
Case Details
Entered Date:
12/06/2006
Applicant:
GAMMA DELTA HOLDING CORP
Description:
inspections
Outstanding Inspections
Case Number: T06FR02838
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| COMPLIANCE | None | Not Inspected |
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR02838
Case Description: INSPECTION
Total Completed Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/06/2006 | INSP - REINSPECTION | EGRIFFIN | Approved | 1). 1). Sprinkler test and inspection report shall be submitted. All repairs shall be completed. IFC 901.6 2). Repair hole in entrance. IFC 703.1 3). Repair fire alarm. IFC 901.6 4). Clean lint form laundry room. IFC 304.1 5). Clean kitchen hood vent. Certificate shall be required for cleaning. IFC 904.11.6.3 6). Cut and remove weeds outside. IFC 314 In addition the following was found on reinspection: 7). Weeds are blocking fire dept sprinkler connection. IFC 901.6 |
| 12/06/2006 | INSP - FULL | EGRIFFIN | Approved | 1). Sprinkler test and inspection report shall be submitted. All repairs shall be completed. IFC 901.6 2). Repair hole in entrance. IFC 703.1 3). Repair fire alarm. IFC 901.6 4). Clean lint form laundry room. IFC 304.1 5). Clean kitchen hood vent. Certificate shall be required for cleaning. IFC 904.11.6.3 6). Cut and remove weeds outside. IFC 314 |