Inspection History Details
Inspection Status: Approved
Inspection History: INSP - REINSPECTION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/30/2007 | INSP - REINSPECTION | Approved | approved | |
| 12/06/2006 | INSP - REINSPECTION | Violation | 1). 1). Sprinkler test and inspection report shall be submitted. All repairs shall be completed. IFC 901.6 2). Repair hole in entrance. IFC 703.1 3). Repair fire alarm. IFC 901.6 4). Clean lint form laundry room. IFC 304.1 5). Clean kitchen hood vent. Certificate shall be required for cleaning. IFC 904.11.6.3 6). Cut and remove weeds outside. IFC 314 In addition the following was found on reinspection: 7). Weeds are blocking fire dept sprinkler connection. IFC 901.6 |