Case: T06FR02812
Case Details
Entered Date:
12/01/2006
Applicant:
HOLUALOA CENTRE EAST OFFICE LLC
Description:
FULL FIRE INSPECTION 3 YR INSPECTION CYCLE
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR02812
Case Description: INSPECTION
Total Completed Inspections - 4
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/01/2006 | VIOL - PRECAUTION AGAINST FIRE | MWAINWRI | Approved | IFC 2003 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. 1. KEEP ALL STORAGE 18 INCHES BELOW SPRINKLER HEAD. |
12/01/2006 | VIOL - FIRE PROTECTION SYSTEMS | MWAINWRI | Approved | IFC 2003 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. SPRINKLER HEAD IN CLOSET OF OFFICE 21 IS LOOSE. 1. SPRINKLER PIPING NEEDS TO BE SECURED. |
12/01/2006 | VIOL - MEANS OF EGRESS | MWAINWRI | Approved | IFC 2003 1011.5.3 Power source. Exit signs shall be illuminated at all times. MULTIPLE EXIT SIGNS UNABLE TO TEST BACKUP POWER. 1. MUST DEMOSTRATE THESE EXIT SIGNS HAVE BACKUP POWER. 2. REPAIR BACKUP POWER TO EXIT SIGN IN FRONT OF OFFICE 21. |
12/01/2006 | INSP - FULL | MWAINWRI | Approved |