Entered Date:

11/30/2006

Applicant:

FIRST AVE/WETMORE OFFICE PLAZA LLC

Description:

FULL FIRE INSPECTION

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR02807
Case Description: INSPECTION
Total Completed Inspections - 5
End Date Description Inspector Results Comments
11/30/2006 VIOL - FIRE SERVICE FEATURES SHIGGINB Approved 505.1 Address numbers. New and existing buildings shall have approved address numbers, 1. SUIT NUMBERING TO CONFUSING, MUST RENUMBER SURGIAL SUIT.
11/30/2006 VIOL - COMPRESSED GASES SHIGGINB Approved 3006.2.1 One-hour exterior rooms. A 1-hour exterior room shall be a room or enclosure separated from the remainder of the building by fire barriers with a fire-resistance rating of not less than 1 hour. Openings between the room or enclosure and interior spaces shall be self-closing smokeand draft-control assemblies having a fire protection rating of not less than 1 hour. Rooms shall have at least one exterior wall that is provided with at least two vents. Each vent shall not be less than 36 square inches (0.023 m2) in area. One vent shall be within 6 inches (152 mm) of the floor and one shall be within 6 inches (152 mm) of the ceiling. Rooms shall be provided with at least one automatic sprinkler to provide container cooling in case of fire. 1. GAS ROOM NEED A SPRINKLER HEAD, PREMIT IS REQUIERED. 2. UPPER VENT IS TO LOW FROM CEILING MUST BE 6 ". BOTTOM VENT IS OK. VENTILATION OPTIONS: 1. RASE VENT TO WITH IN 6" OF CEILING. 2. LOWER CEILING TO 7' WITH A 1 HR RATEING AND RASE VENT IN DOOR TO THE TOP OF DOOR. IF O2 CONTROLS ARE TO HIGH A 1 HR RATED COVER MAY BE USE INSTEAD OF LOWERING CONTROLS. MAX. CYCLINDERS WITH IMPROMENTS IS 8
11/30/2006 VIOL - HAZARDOUS MATERIALS,GEN SHIGGINB Approved 2703.5 Hazard identification signs. Unless otherwise exempted by the fire code official, visible hazard identification signs as specified in NFPA 704 for the specific material contained shall be placed on stationary containers and above-ground tanks and at entrances to locations where hazardous materials are stored, dispensed, used or handled in quantities requiring a permit and at specific entrances and locations designated by the fire code official. 1. MUST PLACE NFPA 704 SIGN SPECIFIED FOR MEDICAL O2 ON THE ENTERANCE AND DOOR TO GAS ROOM
11/30/2006 VIOL - HAZARDOUS MATERIALS,GEN SHIGGINB Approved 2703.4 Material Safety Data Sheets. Material Safety Data Sheets (MSDS) shall be readily available on the premises for hazardous materials regulated by this chapter.
11/30/2006 INSP - FULL SHIGGINB Approved tHIS INSPECTION IS FOR THE SURGERY SIDE ONLY. ALL VIOLATION ARE FOR THE MEDICAL GAS ROOM ONLY.