Case: T06FR02807

Parcel: 10510062G

Inspection Status: Approved

Inspection History: VIOL - COMPRESSED GASES

Case Number - T06FR02807

Inspection Description - VIOL - COMPRESSED GASES

Inspection Status - Approved

Date Description Inspector Results Comments
03/27/2007 VIOL - COMPRESSED GASES Approved
11/30/2006 VIOL - COMPRESSED GASES Violation 3006.2.1 One-hour exterior rooms.
A 1-hour exterior room shall be a room or enclosure separated from the remainder of the building by fire barriers with a fire-resistance
rating of not less than 1 hour. Openings between the room or
enclosure and interior spaces shall be self-closing smokeand draft-control assemblies having a fire protection rating
of not less than 1 hour. Rooms shall have at least one exterior
wall that is provided with at least two vents. Each vent shall
not be less than 36 square inches (0.023 m2) in area. One vent shall be within 6 inches (152 mm) of the floor and one shall be within 6 inches (152 mm) of the ceiling. Rooms shall be provided with at least one automatic sprinkler to provide container cooling in case of fire.
1. GAS ROOM NEED A SPRINKLER HEAD, PREMIT IS REQUIERED.
2. UPPER VENT IS TO LOW FROM CEILING MUST BE 6 ". BOTTOM VENT IS OK.

VENTILATION OPTIONS:
1. RASE VENT TO WITH IN 6" OF CEILING.
2. LOWER CEILING TO 7' WITH A 1 HR RATEING AND RASE VENT IN DOOR TO THE TOP OF DOOR. IF O2 CONTROLS ARE TO HIGH A 1 HR RATED COVER MAY BE USE INSTEAD OF LOWERING CONTROLS.
MAX. CYCLINDERS WITH IMPROMENTS IS 8