Case: T06FR02781
Case Details
Entered Date:
11/28/2006
Applicant:
RAYMOND OBULIA
Description:
FULL FIRE INSPECTION, CHECK LIST USED
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR02781
Case Description: INSPECTION
Total Completed Inspections - 12
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/28/2006 | VIOL - FIRE SERVICE FEATURES | SHIGGINB | Approved | 1. TFC 2003 505.1 Addressing All building will have approved address numbers plainly legible & visible from the street fronting the property. Min. 3” high w/ contrasting background. 1. NEED TO PLACE 3" ADDRESS NUMBERS ON BUILDING. |
| 11/28/2006 | INSP - FULL | SHIGGINB | Approved | ASSISTED LIVING LIC 10 3YR. INSPECTION CYCLE |
| 11/30/2006 | VIOL - FIRE PROTECTION SYSTEMS | SHIGGINB | Approved | 32. TFC 907.2.10 Smoke alarms Check for operation and location. Min. is bedrooms and hallway. 1. NEED A SMOKE ALARM IN LIVING AREA BETWEEN DINING ROOM AND SE BEDROOM |
| 11/30/2006 | VIOL - FIRE RESIST.RATED CONST | SHIGGINB | Approved | 18.TFC 703.1Must be repair w/ fire resistive materials Look behind washers and dryers, hot water heaters, heater closets. 1. REPAIR DRY WALL IN HEATER CLOSET |
| 11/30/2006 | VIOL - MEANS OF EGRESS | SHIGGINB | Approved | 28. TFC 1025.1 General emergency escape and rescue. Is required in all sleeping area. 1. MID BEDROMM NEED A SECONDARY EXIT |
| 11/30/2006 | VIOL - MEANS OF EGRESS | SHIGGINB | Approved | 29. TFC 1027.2 Must be able to use easily and reliable Check if they open and look at security devices 1. REMOVE STICK THST IS USE AS A LOCK FROM SLIDER IN SW BEDROOM |
| 11/30/2006 | VIOL - MEANS OF EGRESS | SHIGGINB | Approved | 26.TFC 1008.18 Door operation No double key dead-bolt locks, no special knowledge needed, no slide bolt locks. Only one unlatching device, Except group R’s can have night latch, indicating dead bolt, or security chain on exits only 1. REMOVE DOUBLE KEY DEAD BOLT FROM LAUNTRY ROOM EXIT, MAY HAVE A THUMB LATCH TYPE DEAD BOLT 2. REMOVE OR DISABLE DOULD KEY DEAD BOLT BETWEEN KITCHEN AND LAUNTRY ROOM |
| 11/30/2006 | VIOL - PRECAUTION AGAINST FIRE | SHIGGINB | Approved | 19. Section 316.1 General. The hood system is part of the cooking appliance and must be kept free of grease. If this has a problem, then there be others 1. NEED TO HAVE A FILTER IN HOOD ABOVE THE RANGE |
| 11/30/2006 | VIOL - ADMINISTRATION | SHIGGINB | Approved | 12. TFC 102.3 Change of use of a building Must have it posted, must have correct occupancy type, and licensed amount must match occupancy class. R3 or R4 Date of C/O defines TFC used for regulation. 1. pOST C OF O |
| 11/30/2006 | VIOL - BUILDING SVCS & SYSTEMS | SHIGGINB | Approved | 23.TFC 603.1 & 316.2 Fuel fired appliances and house cleaning. Furnaces, dryer and hot water heaters are all heat sources and must be maintained and cleaned. 1.RETAP VENT PIPE JOINTS |
| 11/30/2006 | VIOL - BUILDING SVCS & SYSTEMS | SHIGGINB | Approved | 21.TFC 605.4 Multi-plugs and power-taps UL listed,No end to end, home made 1. MULIT-PLUG ADAPTER MUST HAVE A TRIP BUTTOM |
| 11/30/2006 | VIOL - BUILDING SVCS & SYSTEMS | SHIGGINB | Approved | 20. TFC 605.5 Extension cords Grounds, used as permanent wiring, run under carpet, attached to walls can be replaced w/ power strip that has overcurrent protection 1. iMPROPER USE OF POWER TAPS IN NW BEDROOM UNDER BED AND AC UNIT |