Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

11/07/2006

Applicant:

LCC-1ST/WETMORE LLC

Description:

UST

Outstanding Inspections

Case Number: T06FR02723
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
11/07/2006 VIOL - ADMINISTRATION JLANGEJA Violation IFC 109.2.4- Unauthorized tampering of tags is prohibited.
11/07/2006 VIOL - ADMINISTRATION JLANGEJA Violation IFC 110.1.1- Unsafe Condition
11/07/2006 VIOL - MOTOR FUEL DISPENSING JLANGEJA Violation IFC 2203.2- Emergency disconnects shall be located within 100' but not less than 20' from a fuel dispenser. The #5 island has been "red tagged" and shall not be used. Power has been shut off and fuel impact valves shall be tripped.

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR02723
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
12/05/2006 INSP - REINSPECTION JLANGEJA Approved Dispenser that was red tagged has been removed.
12/21/2006 INSP - AST/UST JLANGEJA Approved Met with Bob and Kyle to discuss locations of bollards.