Case: T06FR02723

Parcel: 10510089H


Addresses:

4390 N 1ST AV


Inspection Status: Continued

Inspection History: INSP - AST/UST

Case Number - T06FR02723

Inspection Description - INSP - AST/UST

Inspection Status - Continued

Date Description Inspector Results Comments
12/21/2006 INSP - AST/UST Continued Met with Bob and Kyle to discuss locations of bollards.
12/18/2006 INSP - AST/UST Approved Final inspection passed on 12/14/06 pending electrical final before opening. Vehicle impact protection required for 2 south dispensers, field notice issued.
12/05/2006 INSP - AST/UST Approved Primary piping has been completed, soap tested all joints and passed, OK to bury.
11/30/2006 INSP - AST/UST Continued received test certificates from Westest, Inc, all passed.
11/07/2006 INSP - AST/UST Approved Partial primary, secondary piping inspected, OK to bury. As builts to show piping location. Added 2nd E-stop location to W side of dispensers.