Case Details

Status:

FIELD

Type:

COMPLAINT (COMMERCIAL)

Entered Date:

10/04/2006

Applicant:

WOOD PRINTERS INC

Description:

caller states company As Wood Printers 1063 E. 36th St suite 101 has locked emgency exit not able to exit through the inside, please call David back at 750-3295 with results

Outstanding Inspections

Case Number: T06FR02641
Case Status: FIELD
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
10/05/2006 INSP - FULL RSUMMERS Correction Required jdavis2 assigned.
10/06/2006 VIOL - MEANS OF EGRESS JDAVIS Correction Required 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. This buliding is not occupied at the time and there was a lock put on the outside of the rear door to prevent entry. Someone also had installed a slide-bolt on the inside of the door at some point which is also a fire code violation. I spoke to the owner of the building and gave him until Wednesday October 11, 2006 to abate both issues the issue. I also spoke to the complainant who appearantly was the previous occupant and advised him of my findings.