Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T06FR02587
Case Details
Entered Date:
09/18/2006
Applicant:
CITY OF TUCSON
Description:
AST removal
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR02587
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/18/2006 | INSP - AST/UST | JLANGEJA | Approved | 1000 gallon fuel AST was permitted for removal. Southwest Hazard Control (Eric) inerted the AST with 75# CO2. It purged at <3% O2. All openings were plugged and a 1/4" hole was placed in a bung to prevent overpressurization. All piping was removed. Catclaw Contractors (Aaron Holmes) lifted the tank into a trailor from Tucson Iron & Metal. The truck was placarded appropriately prior to leaving the site. AST is OOS. |