Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

09/14/2006

Applicant:

ESQUIBEL MARY-JOYCE & JOSEPH J JT/RS

Description:

inspection

Outstanding Inspections

Case Number: T06FR02577
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
COMPLIANCE None Not Inspected

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR02577
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
10/19/2006 VIOL - FIRE PROTECTION SYSTEMS EGRIFFIN Approved On 9-14-06, a letter was sent to the above address indicated our concern for some components of the fire alarm system in accordance with NFPA 72, The National Fire Alarm Code. Specifically, the non-listed devices on the fire alarm system are a concern to The Tucson Fire Department Fire Prevention Division. Currently a switch commonly found to turn lights on and off, is being used as an initiating device for the fire alarm system. Plans submitted require a Class A Fire alarm system. This is not a listed component of a Class A fire alarm system. A certificate or written documentation for an approved contractor indicating all components meets NFPA for a Class A fire alarm system You current contractor SimlexGrinnell is aware of these requirements
12/22/2006 INSP - REINSPECTION EGRIFFIN Approved Thank for the information on the fire alarm system. On 9-14-06, a letter was sent to the above address indicated our concern for some components of the fire alarm system in accordance with NFPA 72, The National Fire Alarm Code. Specifically, the non-listed devices on the fire alarm system are a concern to The Tucson Fire Department Fire Prevention Division. Currently a switch commonly found to turn lights on and off, is being used as an initiating device for the fire alarm system. Plans submitted require a Class A Fire alarm system. This is not a listed component of a Class A fire alarm system. A certificate or written documentation for an approved contractor indicating all components meets NFPA for a Class A fire alarm system You current contractor SimlexGrinnell is aware of these requirements. Please submit information indicating light switch type device is listed for fire alarm usage. This letter is to inform you that abatement of these Tucson Fire Code violations must be completed by 1-7-07 A re-inspection shall be conducted at that time to ensure compliance. Failure to comply with these Tucson Fire Code requirements could result in civil litigation under; City of Tucson Ordinance 9609.