Case Details

Status:

FIELD

Type:

INSPECTION

Entered Date:

08/11/2006

Applicant:

WEIL MARTIN J

Description:

full inspection

Outstanding Inspections

Case Number: T06FR02408
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
08/11/2006 INSP - FULL FCONTRER Violation exit signs 1hr. fire door office to chemical room. chemicals need to be labeled.this is the compress cylinders storage area. electrical outlet missing cover plate next to gas heater check all exit doors to make sure they are marked exit,for emergency exit. the large lab room needs another exit door. all emergency exit doors shall have the thumb latch to exit with out a key. Housekeeping in shop areas. Storage shall be 3 feet from electrical panel. The storage of gases,nitrogen,carbon dioxide, hydrogen, oxygen shall have a leak detection alarm,inside for workers and outside the building for fire department emergency responders. The gas lines that are connected to the cylinders and running to the equipment shall be labeled and secured in a approved manner.supply lines from H2 HE flammable, to the equipment shall be of noncombustable material. The plastic supply tubing will melt in a fire.