Case: T06FR02408

Parcel: 115160470

Inspection Status: Violation

Inspection History: INSP - FULL

Case Number - T06FR02408

Inspection Description - INSP - FULL

Inspection Status - Violation

Date Description Inspector Results Comments
08/11/2006 INSP - FULL Violation exit signs
1hr. fire door office to chemical room.
chemicals need to be labeled.this is the compress cylinders storage area.
electrical outlet missing cover plate next to gas heater
check all exit doors to make sure they are marked exit,for emergency exit.
the large lab room needs another exit door.
all emergency exit doors shall have the thumb latch to exit with out a key.
Housekeeping in shop areas.
Storage shall be 3 feet from electrical panel.
The storage of gases,nitrogen,carbon dioxide, hydrogen, oxygen shall have a leak detection alarm,inside for workers and outside the building for fire department emergency responders.
The gas lines that are connected to the cylinders and running to the equipment shall be labeled and secured in a approved manner.supply lines from H2 HE flammable, to the equipment shall be of noncombustable material. The plastic supply tubing will melt in a fire.