Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

COMPLAINT (COMMERCIAL)
Address:

Entered Date:

06/21/2006

Applicant:

BURR-BROWN RESEARCH CORP

Description:

complaint inspection

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR02063
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
End Date Description Inspector Results Comments
06/21/2006 COMPL - INITIAL INSPECTION JVALENZU Approved Per United Fire insp report; "activation of system does not shut down electrical power under hood" Upon consult with electrician and maint staff - all electrical plugs, appliances are on shunt-trip breakers that turn off upon activation of the system. The hood fans have been removed from the system to allow them to operate after system activation until manually turned off. No other deficiencies noted - Staff made change upon direction by David Mann.