Inspection History Details
Inspection Status: Approved
Inspection History: COMPL - INITIAL INSPECTION
Case Number - T06FR02063
Inspection Description - COMPL - INITIAL INSPECTION
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/21/2006 | COMPL - INITIAL INSPECTION | Approved | Per United Fire insp report; "activation of system does not shut down electrical power under hood" Upon consult with electrician and maint staff - all electrical plugs, appliances are on shunt-trip breakers that turn off upon activation of the system. The hood fans have been removed from the system to allow them to operate after system activation until manually turned off. No other deficiencies noted - Staff made change upon direction by David Mann. |