Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

06/21/2006

Applicant:

FOOTHILLS BUSINESS VENTURES LLC

Description:

Full Inspection

Outstanding Inspections

Case Number: T06FR02060
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
06/05/2006 VIOL - ADMINISTRATION NSPRENGE Violation IFC 2003 102.3 The provicions of the International existing Building Code shall apply to all buildings undergoing a change of Occupancy. Acquire and post a current Certificate of Occupancy.
06/05/2006 VIOL - BUILDING SVCS & SYSTEMS NSPRENGE Violation IFC 2003 605.3 A working space of not less than 30 inches wide, 36 inches in depth and 78 inches in height shall be provided in front of electrical panel. Move boxes and obstacles blocking clearance.
06/05/2006 VIOL - BUILDING SVCS & SYSTEMS NSPRENGE Violation IFC 2003 605.5 Extension cords and flexible cords shall not be a substitute for permanent wiring. Remove extension cord in W entrance to stock area.
06/05/2006 VIOL - BUILDING SVCS & SYSTEMS NSPRENGE Violation IFC 2003 605.6 Open junction boxes are prohibited. Replace cover on junction box in stock room (on ceiling).
06/05/2006 VIOL - FIRE PROTECTION SYSTEMS NSPRENGE Violation IFC 2003 901.4.4 Any device that has the appearance of life safety or fire protection equipment, but does not perform that function is prohibited. 901.6 Non required fire protection systems and equipment shall be inspected, tested and maintained or removed. Recharge an dhave extinguisher inspected or remove from facility. Must be mounted on wall bracket if kept.
06/05/2006 VIOL - MEANS OF EGRESS NSPRENGE Violation IFC 2003 1013.4.1 Minimum clear aisle width for a gruop M occupancy shall not be less than 36 inches where part of an exit.
06/05/2006 VIOL - MEANS OF EGRESS NSPRENGE Violation IFC 2003 1027.2 Exit accesses shall be continuously maintained free from obstructions or impendiments to full instant use. Clear stock away from exit and mainain exit sidth on access to the exit.

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR02060
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
06/21/2006 COMPL - REINSPECTION NSPRENGE Approved All violations are corrected, and business is in compliance.