Case: T06FR02060
Case Details
Entered Date:
06/21/2006
Applicant:
FOOTHILLS BUSINESS VENTURES LLC
Description:
Full Inspection
Outstanding Inspections
Case Number: T06FR02060
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 06/05/2006 | VIOL - ADMINISTRATION | NSPRENGE | Violation | IFC 2003 102.3 The provicions of the International existing Building Code shall apply to all buildings undergoing a change of Occupancy. Acquire and post a current Certificate of Occupancy. |
| 06/05/2006 | VIOL - BUILDING SVCS & SYSTEMS | NSPRENGE | Violation | IFC 2003 605.3 A working space of not less than 30 inches wide, 36 inches in depth and 78 inches in height shall be provided in front of electrical panel. Move boxes and obstacles blocking clearance. |
| 06/05/2006 | VIOL - BUILDING SVCS & SYSTEMS | NSPRENGE | Violation | IFC 2003 605.5 Extension cords and flexible cords shall not be a substitute for permanent wiring. Remove extension cord in W entrance to stock area. |
| 06/05/2006 | VIOL - BUILDING SVCS & SYSTEMS | NSPRENGE | Violation | IFC 2003 605.6 Open junction boxes are prohibited. Replace cover on junction box in stock room (on ceiling). |
| 06/05/2006 | VIOL - FIRE PROTECTION SYSTEMS | NSPRENGE | Violation | IFC 2003 901.4.4 Any device that has the appearance of life safety or fire protection equipment, but does not perform that function is prohibited. 901.6 Non required fire protection systems and equipment shall be inspected, tested and maintained or removed. Recharge an dhave extinguisher inspected or remove from facility. Must be mounted on wall bracket if kept. |
| 06/05/2006 | VIOL - MEANS OF EGRESS | NSPRENGE | Violation | IFC 2003 1013.4.1 Minimum clear aisle width for a gruop M occupancy shall not be less than 36 inches where part of an exit. |
| 06/05/2006 | VIOL - MEANS OF EGRESS | NSPRENGE | Violation | IFC 2003 1027.2 Exit accesses shall be continuously maintained free from obstructions or impendiments to full instant use. Clear stock away from exit and mainain exit sidth on access to the exit. |
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR02060
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/21/2006 | COMPL - REINSPECTION | NSPRENGE | Approved | All violations are corrected, and business is in compliance. |