Case: T06FR02060

Parcel: 11307088B


Addresses:

3025 N CAMPBELL AV


Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T06FR02060

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
06/05/2006 VIOL - BUILDING SVCS & SYSTEMS Violation IFC 2003 605.5 Extension cords and flexible cords shall not be a substitute for permanent wiring. Remove extension cord in W entrance to stock area.
06/05/2006 VIOL - BUILDING SVCS & SYSTEMS Violation IFC 2003 605.6 Open junction boxes are prohibited. Replace cover on junction box in stock room (on ceiling).
06/05/2006 VIOL - BUILDING SVCS & SYSTEMS Violation IFC 2003 605.3 A working space of not less than 30 inches wide, 36 inches in depth and 78 inches in height shall be provided in front of electrical panel. Move boxes and obstacles blocking clearance.