Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T06FR02060
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Violation
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/05/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | IFC 2003 605.5 Extension cords and flexible cords shall not be a substitute for permanent wiring. Remove extension cord in W entrance to stock area. | |
| 06/05/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | IFC 2003 605.6 Open junction boxes are prohibited. Replace cover on junction box in stock room (on ceiling). | |
| 06/05/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | IFC 2003 605.3 A working space of not less than 30 inches wide, 36 inches in depth and 78 inches in height shall be provided in front of electrical panel. Move boxes and obstacles blocking clearance. |