Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T06FR01893
Case Details
Entered Date:
06/08/2006
Applicant:
QUIK MART FOOD STORES INC
Description:
Inspection
Outstanding Inspections
Case Number: T06FR01893
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/08/2006 | INSP - LIFE SAFETY | JLANGEJA | Correction Required | North island dispenser has been damaged due to motor vehicle crash. Dispenser shall remain out of service until all inspections are approved. This includes obtaining a permit for work, electrical final, fire final and either replacement of dispenser or repair of dispenser with recertification of listing. Per TFC 2206.7.1- Electrical equipment, dispensers, hose, nozzles and submersible or sub-surface pumps used in fuel-dispensing systems shall be listed. Links to dispenser have been tripped and electrical shut off. Service panel has been RED TAGGED. |
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR01893
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/21/2006 | COMPL - REINSPECTION | JLANGEJA | Approved | MA19 did final on new dispenser. Red Tag removed and system back in service. |