Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

06/08/2006

Applicant:

QUIK MART FOOD STORES INC

Description:

Inspection

Outstanding Inspections

Case Number: T06FR01893
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
06/08/2006 INSP - LIFE SAFETY JLANGEJA Correction Required North island dispenser has been damaged due to motor vehicle crash. Dispenser shall remain out of service until all inspections are approved. This includes obtaining a permit for work, electrical final, fire final and either replacement of dispenser or repair of dispenser with recertification of listing. Per TFC 2206.7.1- Electrical equipment, dispensers, hose, nozzles and submersible or sub-surface pumps used in fuel-dispensing systems shall be listed. Links to dispenser have been tripped and electrical shut off. Service panel has been RED TAGGED.

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR01893
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
06/21/2006 COMPL - REINSPECTION JLANGEJA Approved MA19 did final on new dispenser. Red Tag removed and system back in service.