Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Correction Required
Inspection History: INSP - LIFE SAFETY
Case Number - T06FR01893
Inspection Description - INSP - LIFE SAFETY
Inspection Status - Correction Required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/08/2006 | INSP - LIFE SAFETY | Correction Required | North island dispenser has been damaged due to motor vehicle crash. Dispenser shall remain out of service until all inspections are approved. This includes obtaining a permit for work, electrical final, fire final and either replacement of dispenser or repair of dispenser with recertification of listing. Per TFC 2206.7.1- Electrical equipment, dispensers, hose, nozzles and submersible or sub-surface pumps used in fuel-dispensing systems shall be listed. Links to dispenser have been tripped and electrical shut off. Service panel has been RED TAGGED. |