05/24/2006

Applicant:

TANG PROPERTIES LLC

Description:

Sips Full

Outstanding Inspections

Case Number: T06FR01456
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
INSP - SELF INSPECTION PROGRAM None Not Inspected
04/20/2006 INSP - FULL NSPRENGE Correction Required
04/20/2006 VIOL - ADMINISTRATION NSPRENGE Violation IFC 2003 102.4 Repairs, alterations, and additions to existing structures shall comply with the International Building Code or New Jersey Rehabilitation Subcode. Acquire and post a C of O for building.
04/20/2006 VIOL - BUILDING SVCS & SYSTEMS NSPRENGE Violation IFC 2003 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. Remove balasts placed against and adjacent to the electrical panel.
04/20/2006 VIOL - BUILDING SVCS & SYSTEMS NSPRENGE Violation IFC 2003 605.5 Extension cords shall not be used as a source for permanent wiring. Remove extension cord powering the fan in the back hallway.
04/20/2006 VIOL - BUILDING SVCS & SYSTEMS NSPRENGE Violation IFC 2003 605.6 Open wiring splices are prohibited. Install an approved junction box to contain wires:in rear storage area in ceiling hole in storage room.
04/20/2006 VIOL - MEANS OF EGRESS NSPRENGE Violation IFC 2003 1008.1.8.3 The use of a double key locking cylinder on a main exit requires a sign on the egress side of the door or adjacent to it, stating: "This door to remain unlocked during business hours or when building is occupied." Acquire and post this sign in 1 " letteriing.
06/08/2006 INSP - REINSPECTION NSPRENGE Partial Approval Sign posted over door. Electric panel is cleared. Open wiring splices removed. Extension cord removed. No C of O yet. Gave notice of intention to precite for lack of acquiring a C of O.

Completed Inspections

Case Status: FIELD
Case Number: T06FR01456
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
06/14/2006 COMPLIANCE NSPRENGE Approved C of O obtained. Business is in compliance and approved.