Inspection Status: Violation
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T06FR01456
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Violation
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/20/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | IFC 2003 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. Remove balasts placed against and adjacent to the electrical panel. | |
| 04/20/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | IFC 2003 605.6 Open wiring splices are prohibited. Install an approved junction box to contain wires:in rear storage area in ceiling hole in storage room. | |
| 04/20/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | IFC 2003 605.5 Extension cords shall not be used as a source for permanent wiring. Remove extension cord powering the fan in the back hallway. |