Case: T06FR01456

Parcel: 11310275A


Addresses:

2523 N CAMPBELL AV


Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T06FR01456

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
04/20/2006 VIOL - BUILDING SVCS & SYSTEMS Violation IFC 2003 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. Remove balasts placed against and adjacent to the electrical panel.
04/20/2006 VIOL - BUILDING SVCS & SYSTEMS Violation IFC 2003 605.6 Open wiring splices are prohibited. Install an approved junction box to contain wires:in rear storage area in ceiling hole in storage room.
04/20/2006 VIOL - BUILDING SVCS & SYSTEMS Violation IFC 2003 605.5 Extension cords shall not be used as a source for permanent wiring. Remove extension cord powering the fan in the back hallway.