Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

04/07/2006

Applicant:

MAVIN CAPITAL LLC

Description:

Sips - Full Inspection

Outstanding Inspections

Case Number: T06FR00699
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
04/07/2006 VIOL - BUILDING SVCS & SYSTEMS NSPRENGE Violation IFC 2003 605.4 Multiplug adapters are prohibited. Remove multiplug adapters from reception area behind desks on the North and East walls.
04/07/2006 VIOL - BUILDING SVCS & SYSTEMS NSPRENGE Violation IFC 2003 605.5 Extension cords shall not be used as a source for permanent wiring. Remove two extension cords used in the reception area, and cord in office.
04/07/2006 VIOL - BUILDING SVCS & SYSTEMS NSPRENGE Violation IFC 2003 605.6 Open junction boxes shall be covered and all electrical outlets shall have cover plates. Put a cover on wall outlet near rear exit and floor outlet in SW most room.
04/07/2006 VIOL - MEANS OF EGRESS NSPRENGE Violation IFC 2003 1008.1.8.3 Doors with a double key locking cylinder need a sign posted on the door that states..." This door to remain unlocked during business hours."
04/07/2006 VIOL - MEANS OF EGRESS NSPRENGE Violation IFC 2003 1027.2 Means of egress shall be free from obstructions that prevent its use. Remove sofa blocking rear exit door and pathway.

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR00699
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
05/02/2006 INSP - REINSPECTION NSPRENGE Approved
05/02/2006 INSP - REINSPECTION NSPRENGE Approved Sign on door. All violations corrected and business is now in compliance.