Inspection Status: Violation
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date |
Description |
Inspector |
Results |
Comments |
| 04/07/2006 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Violation |
IFC 2003 605.4 Multiplug adapters are prohibited. Remove multiplug adapters from reception area behind desks on the North and East walls. |
| 04/07/2006 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Violation |
IFC 2003 605.5 Extension cords shall not be used as a source for permanent wiring. Remove two extension cords used in the reception area, and cord in office. |
| 04/07/2006 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Violation |
IFC 2003 605.6 Open junction boxes shall be covered and all electrical outlets shall have cover plates. Put a cover on wall outlet near rear exit and floor outlet in SW most room. |