Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T06FR00699
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/07/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | IFC 2003 605.4 Multiplug adapters are prohibited. Remove multiplug adapters from reception area behind desks on the North and East walls. | |
04/07/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | IFC 2003 605.5 Extension cords shall not be used as a source for permanent wiring. Remove two extension cords used in the reception area, and cord in office. | |
04/07/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | IFC 2003 605.6 Open junction boxes shall be covered and all electrical outlets shall have cover plates. Put a cover on wall outlet near rear exit and floor outlet in SW most room. |