Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

04/03/2006

Applicant:

18 CENTRAL LLC 59.77% & FAITSCH CHRISTOPHER D &

Description:

requesting yearly inspection also for military warehouse approval.

Outstanding Inspections

Case Number: T06FR00623
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
04/21/2006 INSP - FULL FCONTRER Correction Required 2003 IFC-315.2 Storage, of combustaible materials shall be 18 inches below sprinkler heads.This is a recommandation to keep in mind when stocking. 2003 IFC- 605.6 Open junction boxes shall be repaired or replace cover plate on outlet. 2003IFC- 605.9 Temporary wiring attached to a structure shall be attached in an approved manner. Exposed wiring shall be repaired. 2003 IFC-605.5.2 A working space and clearance of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment (panel). 2003 IFC-310.3 No Smoking signs shall be posted throughout the warehouse in conspicuous locations. The warehouse has a sprinkler system that is monitored by central alarm. There is moke detectors throughout and a fire alarm system. I will follow up in two weeks to do the final inspection.