Inspection History Details
Inspection Status: Correction Required
Inspection History: INSP - FULL
Case Number - T06FR00623
Inspection Description - INSP - FULL
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/21/2006 | INSP - FULL | Correction Required | 2003 IFC-315.2 Storage, of combustaible materials shall be 18 inches below sprinkler heads.This is a recommandation to keep in mind when stocking. 2003 IFC- 605.6 Open junction boxes shall be repaired or replace cover plate on outlet. 2003IFC- 605.9 Temporary wiring attached to a structure shall be attached in an approved manner. Exposed wiring shall be repaired. 2003 IFC-605.5.2 A working space and clearance of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment (panel). 2003 IFC-310.3 No Smoking signs shall be posted throughout the warehouse in conspicuous locations. The warehouse has a sprinkler system that is monitored by central alarm. There is moke detectors throughout and a fire alarm system. I will follow up in two weeks to do the final inspection. |
|
04/04/2006 | INSP - FULL | Correction Required | fcontre1 assigned. | |
04/03/2006 | INSP - FULL | Approved | requesting yearly inspection and also for military warehouse approval. |