Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T06FR00385
Case Details
Entered Date:
03/14/2006
Applicant:
LDR ENTERPRISES LLC
Description:
Inspection
Outstanding Inspections
Case Number: T06FR00385
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
INSP - FULL | None | Not Inspected | ||
03/14/2006 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 901.6- Fire extinguishing systems hsall be maintained in operative condition at all times. *Coverage for griddle and stove + rice cooker shall have coverage. *Nozzles shall have grease caps installed. |
03/14/2006 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 904.11.2- The actuation of the fire extinguishing system shall automatically shut down the fuel or electrical power supply to the cooking equipment and all electrical receptacles located within the perimeter of the hood. The resets shall be manual. *I will need documentation that the gas and electricity is shut off upon activation of the fire extinguishing system. This must be performed by qualified personnel. |
03/14/2006 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 906.7- Fire extinguishers shall be anchored securely within 30 feet of cooking operations, near an exit. |
03/28/2006 | INSP - REINSPECTION | JLANGEJA | Partial Approval | Coverage for appliances has been corrected. 2 nozzle covers need to be replaced. K class extinguisher needs to be repaired so it can be mounted. |
04/18/2006 | COMPL - REINSPECTION | JLANGEJA | Partial Approval | Reinspection for 5-02-06 TFC 906.7, TFC 904.11.2 still in violation |
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR00385
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/02/2006 | COMPLIANCE | JLANGEJA | Approved | All violations have been corrected. |