Inspection

Outstanding Inspections

Case Number: T06FR00385
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
03/14/2006 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 901.6- Fire extinguishing systems hsall be maintained in operative condition at all times. *Coverage for griddle and stove + rice cooker shall have coverage. *Nozzles shall have grease caps installed.
03/14/2006 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 904.11.2- The actuation of the fire extinguishing system shall automatically shut down the fuel or electrical power supply to the cooking equipment and all electrical receptacles located within the perimeter of the hood. The resets shall be manual. *I will need documentation that the gas and electricity is shut off upon activation of the fire extinguishing system. This must be performed by qualified personnel.
03/14/2006 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 906.7- Fire extinguishers shall be anchored securely within 30 feet of cooking operations, near an exit.
03/28/2006 INSP - REINSPECTION JLANGEJA Partial Approval Coverage for appliances has been corrected. 2 nozzle covers need to be replaced. K class extinguisher needs to be repaired so it can be mounted.
04/18/2006 COMPL - REINSPECTION JLANGEJA Partial Approval Reinspection for 5-02-06 TFC 906.7, TFC 904.11.2 still in violation

Completed Inspections

Case Status: COMPLETE
Case Number: T06FR00385
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
05/02/2006 COMPLIANCE JLANGEJA Approved All violations have been corrected.